]> jspc29.x-matter.uni-frankfurt.de Git - daqdocu.git/commitdiff
update operator notes
authorJan Michel <mail@janmichel.eu>
Sat, 19 Feb 2022 14:09:37 +0000 (15:09 +0100)
committerJan Michel <mail@janmichel.eu>
Sat, 19 Feb 2022 14:09:37 +0000 (15:09 +0100)
hadesoperator/expert_powersupplies.tex
hadesoperator/generalremarks.tex

index 4d640152ad2665b7a4e8a32e16acd639310adfb7..c8ee39cb38fe0cd1eae25c78b091a874267fc594 100644 (file)
@@ -19,7 +19,7 @@ There are several interfaces for control, depending on the supply.
  \item[RichFans] Coolings fans on RICH
  \item[ECal 1/2/3] ECal Padiwa (two channels per sector)
  \item[CentralControls] Channel 1: iTOF Padiwa\\ Channel 2: Trigger fanout at CTS, Triggerbox, 
-Beammonitor\\Channel 3+4: CTS Trb, BLR
+Beammonitor\\Channel 3+4: CTS Trb, BLR, some DCS modules
  \item[STS 1/2] STS Fee
  \item[Start] Channel 2+4: Start Trb \\Channel 1: Start Padiwa\\Channel 3: Start Fans
  \item[Veto] Hodo Trb, Hodo Fee
index ca4c21f9122707d04d59de0ac80a678f76f48551..edcd8d6e175c2a734ec5ff89998e29fcc9639dbe 100644 (file)
@@ -1,12 +1,12 @@
 
 \part{Daily News for the Operator}
 
-\textbf{2022/02/12 - this page will be updated during the beamtime}
+\textbf{2022/02/19}
 \begin{itemize*}
-  \item Always keep an eye on the rate plots (``Main Screen 4'' on the web page). If you notice any 
-asymmetry between sectors / parts of detectors, try to do a reload of thresholds for the detector 
-(do a ``Start Stop DAQ'' before and after to avoid taking corrupted data). If this doesn't help, 
-talk to the detector expert, e.g. a power cycle of the frontends might be necessary.
+  \item Always {\bf keep an eye on the rate plots} (``Main Screen 4'' on the web page). If you 
+notice any asymmetry between sectors / parts of detectors, try to do a reload of thresholds for the 
+detector. If this doesn't help, talk to the detector expert, e.g. a power cycle of the frontends 
+might be necessary.
 \begin{itemize*}
 \item e.g. in ECal a row of 8 green dots appear (-> ECal Padiwa Powercycle)
 \item e.g. in TOF one sector has a lower/higher rate (-> Tresholds TOF)
@@ -15,27 +15,30 @@ talk to the detector expert, e.g. a power cycle of the frontends might be necess
 Special attention is needed after a power cycle!
 
   \item After any of the ``Reboot Hubs`` and DAQ restart: If Eventbuilders do not work, do 
-a ''Fix missing IP`` and another DAQ restart.
+a ''Fix missing IP`` and (if it prints something apart from 'Done') another DAQ restart.
+
+  \item After a break, {\bf Eventbuilders need some time to recover}. Wait a bit and don't try to 
+restart them more than once per minute. Also try to use ''Reset`` from the Web browser EB interface 
+for a 'softer' reset.
+
+  \item In most cases a {\bf reboot of a subsystem is the better option} compared to a power cycle. 
+If all boards of a subsystem are present, do a reboot, but not a power cycle. Check the missing 
+endpoints - {\bf if the boards you want to reboot are missing, it won't work} (apart from MDC).
 
-  \item In most cases a reboot of a subsystem is the better option compared to a power cycle. If 
-all boards of a subsystem are present, do a reboot, but not a power cycle. Check the missing 
-endpoints - if the boards you want to reboot are missing, it won't work.
-\begin{itemize*}
-\item If you do a reboot of DiRich and Combiners at once: Make a short pause after rebooting 
-DiRich, and check there are less than 900 boards missing from RICH. If it's more, do a DAQ restart 
-before rebooting Combiners.
-\end{itemize*}
 
-  \item   There are a couple of recent issues with MDC DAQ, where power cycles or reboots are not 
+  \item   There are a couple of recent issues with MDC, where power cycles or reboots are not 
 necessary:
 \begin{itemize*}
-\item If 9 boards including 1033 are missing: Do DAQ restarts until they are back.
 \item If 2110 and 2112 are missing after a DAQ restart: Restart again. 
 \end{itemize*}
 
-\item If you notice the system to get unstable (frequent restarts), take the time for a full reboot 
-/ power cycle together with the expert. This helps a lot to get a stable system again, especially if 
-the point of failure can not be identified.
+
+\item Many actions can be done {\bf without a DAQ restart}:
+\begin{itemize*}
+\item All actions from the ''Settings`` column can be done while DAQ is running
+\item ''Reset Thresholds STS`` require you to start/stop trigger before and after.
+\item All ''Powercycle Padiwa`` require you to stop trigger before and load thresholds after.
+\end{itemize*}
 
 
 \end{itemize*}