]> jspc29.x-matter.uni-frankfurt.de Git - mvd_epics.git/commitdiff
Updates to Huber_Unistate_425.db
authorPhilipp Klaus <klaus@physik.uni-frankfurt.de>
Mon, 10 Apr 2017 15:03:12 +0000 (17:03 +0200)
committerPhilipp Klaus <klaus@physik.uni-frankfurt.de>
Mon, 10 Apr 2017 15:03:12 +0000 (17:03 +0200)
* bug fix: ASLO was off by 10**4 for writable PVs
* ADEL and MDEL are now 0.05 deg C (instead of 1.0 deg C)
* macro ("variable") renaming:
    * PANDA     -> $(sys)
    * $(subsys) -> $(sub)
    * $(sector) -> $(csys)
* Additional FLNKs for the further PVs

HUBER_COOLING/HUBER_COOLINGApp/Db/Huber_Unistate_425.db

index bd145f3381b02cdd291f465ec2681003294ff99e..edac2f648ece6a7a57c017a709c1270e514f1a61 100644 (file)
@@ -8,91 +8,94 @@
 # ###                                   ### #
 # ### Ref 1.0; 2014-01-07               ### #
 # ###                                   ### #
-# ### macros: subsys  PANDA subsystem   ### #
-# ###         PORT    Asyn Interface    ### #
-# ###         sector  Sector of subsys  ### #
+# ### macros:                           ### #
+# ###         sys   system              ### #
+# ###         sub   subsystem           ### #
+# ###         csys  cooling sub system  ### #
+# ###         PORT  Asyn Interface      ### #
 #############################################
 
-record (ai, "PANDA:$(subsys):COOLING:$(sector):SetpointMom") {
+record (ai, "$(sys):$(sub):COOLING:$(csys):SetpointMom") {
   field (DTYP, "stream")
   field (INP,  "@Huber_Unistate_425.proto getDesVal $(PORT)")  
   field (PINI, "YES")
   field (EGU,  "°C")
   field (PREC, "2")
-  field (ADEL, "1")
-  field (MDEL, "1")
+  field (ADEL, "0.05")
+  field (MDEL, "0.05")
   field (ASLO, "0.01")
   field (AOFF, "0")
 }
 
-record (ai, "PANDA:$(subsys):COOLING:$(sector):BathTemperatureMom") {
+record (ai, "$(sys):$(sub):COOLING:$(csys):BathTemperatureMom") {
   field (DTYP, "stream")
   field (INP,  "@Huber_Unistate_425.proto getBathTemp $(PORT)")
   field (SCAN, "10 second")
-  field (FLNK, "PANDA:$(subsys):COOLING:$(sector):getExtTemp")
+  field (FLNK, "$(sys):$(sub):COOLING:$(csys):ExternalTemperatureMom")
   field (EGU, "°C")
   field (PREC, "2")
-  field (ADEL, "1")
-  field (MDEL, "1")
+  field (ADEL, "0.05")
+  field (MDEL, "0.05")
   field (ASLO, "0.01")
   field (AOFF, "0")
                                              
 }
 
-record (ai, "PANDA:$(subsys):COOLING:$(sector):ExternalTemperatureMom") {
+record (ai, "$(sys):$(sub):COOLING:$(csys):ExternalTemperatureMom") {
   field (DTYP, "stream")
   field (INP,  "@Huber_Unistate_425.proto getExtTemp $(PORT)")
   field (EGU,  "°C")
   field (PREC, "2")
-  field (ADEL, "1")
-  field (MDEL, "1")
+  field (ADEL, "0.05")
+  field (MDEL, "0.05")
   field (ASLO, "0.01")
   field (AOFF, "0")
+  field (FLNK, "$(p):$(sub):COOLING:SetpointMom")
 }
 
 #--------------------------------------------------------------------------------
 
-record (ao, "PANDA:$(subsys):COOLING:$(sector):Setpoint") {
+record (ao, "$(sys):$(sub):COOLING:$(csys):Setpoint") {
   field (DTYP, "stream")
   field (OUT,  "@Huber_Unistate_425.proto setDesVal $(PORT)") 
   field (EGU,  "°C")
   field (PREC, "2")
-  field (ADEL, "1")
-  field (MDEL, "1")
-  field (ASLO, "100")
+  field (ADEL, "0.05")
+  field (MDEL, "0.05")
+  field (ASLO, "0.01")
   field (AOFF, "0")
 }
 
-record (ao , "PANDA:$(subsys):COOLING:$(sector):MinimumValue") {
+record (ao , "$(sys):$(sub):COOLING:$(csys):MinimumValue") {
   field (DTYP, "stream")
   field (OUT,  "@Huber_Unistate_425.proto setMinVal $(PORT)") 
   field (EGU,  "°C")
   field (PREC, "2")
-  field (ADEL, "1")
-  field (MDEL, "1")                                         
-  field (ASLO, "100")
+  field (ADEL, "0.05")
+  field (MDEL, "0.05")                                         
+  field (ASLO, "0.01")
   field (AOFF, "0")
 }
 
-record (ao, "PANDA:$(subsys):COOLING:$(sector):MaximumValue") {
+record (ao, "$(sys):$(sub):COOLING:$(csys):MaximumValue") {
   field (DTYP, "stream")
   field (OUT,  "@Huber_Unistate_425.proto setMaxVal $(PORT)")
   field (EGU,  "°C")
   field (PREC, "2")
-  field (ADEL, "1")
-  field (MDEL, "1")
-  field (ASLO, "100")
+  field (ADEL, "0.05")
+  field (MDEL, "0.05")
+  field (ASLO, "0.01")
   field (AOFF, "0")
 }
 
-record (bo , "PANDA:$(subsys):COOLING:$(sector):TemperatureControl") {
+record (bo , "$(sys):$(sub):COOLING:$(csys):TemperatureControl") {
   field (DTYP, "stream")
   field (OUT,  "@Huber_Unistate_425.proto setTempCtrl $(PORT)")
   field (ZNAM, "OFF")
   field (ONAM, "ON")
 }
 
-record (bo, "PANDA:$(subsys):COOLING:$(sector):TemperatureMode") {
+record (bo, "$(sys):$(sub):COOLING:$(csys):TemperatureMode") {
   field (DTYP, "stream")
   field (OUT,  "@Huber_Unistate_425.proto setTempMode $(PORT)")
   field (ZNAM, "INTERN")