From: Jan Michel Date: Mon, 28 Jan 2019 16:31:57 +0000 (+0100) Subject: update xml-db for TDC trigger windows X-Git-Url: https://jspc29.x-matter.uni-frankfurt.de/git/?a=commitdiff_plain;h=2db8a7f1b190ea610aa9a497ef5ba78c14fb3619;p=daqtools.git update xml-db for TDC trigger windows --- diff --git a/xml-db/database/TDC.xml b/xml-db/database/TDC.xml index 5713b68..a1578f3 100644 --- a/xml-db/database/TDC.xml +++ b/xml-db/database/TDC.xml @@ -103,12 +103,11 @@ Status of the TriggerWindow feature - Trigger window width BEFORE the trigger with + Start of the trigger window. Time BEFORE the trigger with granularity of 5 ns - - Trigger window width AFTER the trigger with - granularity of 5 ns + + End of the trigger window. Before or after the trigger with a granularity of 5 ns and a range from -1023 to +1023. Values 0 to 50 ns are not allowed. Trigger window enabled? @@ -219,11 +218,11 @@ Enables the Debug Mode. Different statistics and debug words are sent after every trigger - + Resets the internal counters @@ -236,21 +235,20 @@ Used to reset the coarse counters. Setting this bit signals for the coarse counter reset but the action will take place with the arrival of the next valid trigger in order to synchronise the coarse counters in a large system. - + Configuration of the TriggerWindow feature - Trigger window width BEFORE the trigger with + Start of the trigger window. Time BEFORE the trigger with granularity of 5 ns - - Trigger window width AFTER the trigger with - granularity of 5 ns. ATTENTION: Minimum value is x"00f"! - + + End of the trigger window. Before or after the trigger with a granularity of 5 ns and a range from -1023 to +1023. Values 0 to 50 ns are not allowed. + Trigger window enable